DirectAire® X2

DirectAire® X2’s ability to deliver high volumes of air directly and evenly across the face of two server racks gives it the capacity to cool very high density equipment in a range of facility designs. DirectAire X2 is specifically designed for use in cold aisles that are only one airflow panel wide. The panel’s angular throw evenly distributes the majority of the air it delivers directly to the face of two opposite facing racks providing virtual containment when used in conjunction with other airflow management best practices.

Pressure (in. H2O)CFM (w/o Damper)kW/Rack (93% CI)
.0211514.2
.0416266.0
.0518446.8
.0620077.4
.0823188.6
.1025949.6
.12282310.4
.14302711.2
.16321711.9
.18337812.5
.20343312.7